- Product Name: Fan Coil Unit
- Item No.:AEFP
- Description:
- Fan coil unit
Chart 1. Performance Parameter
Model
Specifications
AEFP-3.5
AEFP-5
AEFP-6.3
AEFP-8
AEFP-10
AEFP-12.5
AEFP-16
AEFP-20
Air flow
( m3/h)
High
350
510
680
850
1040
1360
1600
2040
Medium
270
400
410
680
850
980
1350
1600
Low
180
260
320
460
670
860
1100
130011 1300
Cooling
Capacity
(KW)
High
2.03
2.96
3.87
4.58
5.29
6.98
8.54
10.65
Medium
1.63
2.36
2.42
3.45
4.98
6.1
7.5
8.10
Low
1.28
1.90
2.1
2.80
4.30
5.20
6.30
6.80
Heating
Capacity
(KW)
High
3.49
5.47
6.80
8.01
9.22
12.4
16.3
19.5
Medium
2.46
3.53
4.56
5.34
7.30
9.38
11.50
14.50
Low
1.68
2.71
3.15
4.2
6.1
8.1
9.51
11.50
Noise(dBA)
</=37
</=39
</=42
</=45
</=47
</=48
</=50
</=53
Input Power
(W)
Standard
30
32
38
60
70
90
110
160
Residual
Pressure
Type
40
50
55
70
90
100
160
200
Water flow
0.35
0.48
0.68
0.78
0.91
1.14
1.47
1.75
Water resistance(Kpa)
15
20
30
35
45
35
40
46
Motor
quantity
WA
1
1
1
1
1
2
2
2
WM.LM.LA
1
1
1
1
1
1
2
2
KMQ
1
1
1
1
1
1
1
Fan
Wheel
quantity
WA
1
2
2
2
2
4
4
4
WM.LM.LA
1
1
2
2
2
2
4
4
KMQ
1
1
2
2
2
2
2
Weight
(kg)
WA
17
18
19
22
26
39
43
49
WM
28
32
36
40
43
59
69
75
LA
20
25
26
30
35
50
60
65
LM
28
32
36
40
43
59
69
75
KMQ
27
30
35
38
42
44
50
Working pressure
1.25
Power
220V 50HZ
Remarks:
Rated air flow is tested when the static pressure at the outlet is 0 Pa .
Cooling parameters: dry-bulb temperature of inlet air is 27 oC.wet –bulb temperature is 19.5 oC, humidity is 49.36% water inlet temperature is 7 oC and water outlet temperature difference is 5 oC.
Heating parameters: dry-bulb temperature of inlet air is 20 oC, water inlet temperature is 60 oC,and the water flow is the same as the cooling conditions.
Model Explanation
6.3 W A X Z
AEFP
Position of water inlet /outlet
Z: left
Y: rightNo mentioned if standard
X: with under return air box
B: with back return air boxInstallation way
A: Concealed
M: Mounted
H: Concealed high-static pressure
Structure
&nb